Region L.V
Expand/Contract AC contactor Series
Expand/Contract SM8 Series Moulded Case Circuit Breaker
Expand/Contract Box Series
Expand/Contract Mini Circuit Breaker Series
Range:
Keyword:
 
Any question?
Enquiry Now
Go Back | Print | Published time: 2006/06/07 13:47
SM-18 - REGION L.V Page Up | Page Down
  Name: SM-18
  Module: SM-18
  Attach 1 : Download

Scope Of Application

       SM18( rated current adjustable ) Series Moulded Case styleCircuit Breaker(hereinafter referred to as SM18) applied to circuit of AC 50 Hz/60 Hz, Rated Voltage 690V or less, direct current rated voltageis 250V or less, rated current up to 800A. It has the functions of overload, short-circuit and lack voltage protection.
      SM18 commonly is used for distribution protection. Rated current In¡Ü400A, it also can be used for electromotor protection, and unfrequently start and stop operation.
         SM18 applied to triphibian use, so as to ship use, enduring humidity, salt fog, mildew and ship normally vibration. For ship use, normally environment temperature is -25¡æ~+45¡æ, product according to Ship Electrical Equipment of IEC92 and Ship Use Low Voltage Electric Basic Requirement of GB/T3783 adn relative regulate .

According To Standard

GB/T14048.1 (egv IEC60947-1)low voltage switch equipment and control equipment general rules
GB 14048.2 (idt IEC60947-2)low voltage switch equipment and control equipment low voltage Circuit Breake

Normally Use Condition

a) altitude of installation location is under 2000m(special requirement should negotiate with manufacturer),
b) ambient air temperature is -25¡æ~+45¡æ, and 24haverage value under +35¡æ(special requirement should negotiate with manufacturer),
c) the highest temperature +40¡æ, air relative humidity 50% or less, lower temperature . It allow higher relative humidity. For example, if 20¡æ upto 90%. The dew coagulated by change of temperature should adopt proper measure (e.g. drain hole),
d) pollution grade 3

Type&Meaning


Structure Characteristic5.1 product shell  adopt insulated good performance, special plastic high in fire-resistance and strength, good electrical and machanical performance;
5.2 can according to requirement provide front, back and insert etc. connection manner;
5.3 rated current rated value Ir1 of thermal long time delay tripping mechanism can adjustable from 0.8In to 1.0In, having adjustable orientation symbol (use point of peak angle of isoceles triangle).of 0.8In, 0.9In and 1.0In . 0.8In and 1.0In is examine point and other position is only for reference;
5.4 Frame Grade Rated Current Inm¡Ý400AµÄCircuit Breaker, Æäinstantaneous action rated value adjustable, adjustable area is 5In~10In, (commonly rated in 10In, special requirement should contact with manufacturer), rated precision is ¡À20%;
5.5 product contactor and arc system have scientific design. In short-circuit breaking capability test, fly arc distance can be zero;
5.6 inside can install accessories separately of minute urgestripping mechanism, lack voltage tripping mechanism, auxiliary contactor and alarm contactor etc. connection of accessories is composed of down-lead manner and terminal manner;
5.7 exterior can adopt electromotion operation wheel , also can adopt knob, gun style and long (only for Inm¡Ý630A)operation handle,and machanical chain equipment ;
5.8 4 poles Circuit BreakerµÄN POLE commonly not with tripping mechanism, close and open at the same time with other 3 poles.For special requirement, it can be either first close and then open (Type D), or connecting directly in-out line end of N Pole (Tyep T).

  

Order notice

Customer should describe each requirement according to all types
Additional, so do rated current. For example, tripping mechanism with the minute urges/lack voltage, should be described AC or direct current and control /out voltage value, such as exterior with manual or dynamoelectric operation equipment etc.

Go Back | Go Top | Print